Double circuit anchor and angle tension poles 110kW

У110-2

Product Name У110-2 У110-2+5 У110-2+9 У110-2+14 У110-2
Glaze Ice Region I-IV I-IV I-IV I-IV
Wind Region III III III III
Wire Model АС-70 ÷
АС-240
АС-70 ÷
АС-240
АС-70 ÷
АС-240
АС-70 ÷
АС-240
Dimensions in Foundation Axis L, m 4,8 6,3 7,5 9,0
Tower Height Н, m 24,7 29,7 33,7 38,7
Height up to Lower Crossarm h, m 10,5 15,5 19,5 24,5
Weight of Tower with Zinc Coating, kg 8014 10074 11820 15191
Standard Project Number 3078тм
Note Towers are used also in mountainous regions when PTL turn angle is limited. This type of tower can be used on 150kV overhead lines.

У110-2В

Product Name У110-2В У110-2В+5 У110-2В
Glaze Ice Region I-IV I-IV
Wind Region III III
Wire Model АС-70 ÷ АС-240 АС-70 ÷ АС-240
Dimensions in Foundation Axis L, m 4,8 6,3
Tower Height Н, m 24,7 29,7
Height up to Lower Crossarm h, m 10,5 15,5
Weight of Tower with Zinc Coating, kg 8178 10234
Standard Project Number 3078тм
Note Towers designed to switch to horizontal configuration.

У110-2П

Product Name У110-2П У110-2П+5 У110-2П+9 У110-2П+14 У110-2П
Glaze Ice Region I-IV I-IV I-IV I-IV
Wind Region III III III III
Wire Model АС-70 ÷
АС-240
АС-70 ÷
АС-240
АС-70 ÷
АС-240
АС-70 ÷
АС-240
Dimensions in Foundation Axis L, m 4,8 6,3 7,5 9,0
Tower Height Н, m 24,7 29,7 33,7 38,7
Height up to Lower Crossarm h, m 10,5 15,5 19,5 24,5
Weight of Tower with Zinc Coating, kg 8168 10224 11975 15344
Standard Project Number 3078тм
Note

Towers used at transition point to vertical configuration (two tiers).

У110-2Т

Product Name У110-2Т У110-2Т+9 У110-2Т
Glaze Ice Region I-IV I-IV
Wind Region III III
Wire Model АС-150 ÷ АС-240 АС-150 ÷ АС-240
Dimensions in Foundation Axis L, m 4,8 7,5
Tower Height Н, m 24,7 33,7
Height up to Lower Crossarm h, m 10,5 19,5
Weight of Tower with Zinc Coating, kg 8016 11823
Standard Project Number 3078тм
Note Possible to use 5m or 8m long lightning rods.

У110-4

Product Name У110-4 У110-4+5 У110-4
Glaze Ice Region I-IV I-IV
Wind Region III III
Wire Model АС-70 ÷ АС-150 АС-70 ÷ АС-150
Dimensions in Foundation Axis L, m 4,1 5,6
Tower Height Н, m 23,9 28,9
Height up to Lower Crossarm h, m 10,5 15,5
Weight of Tower with Zinc Coating, kg 5450 6851
Standard Project Number 3078тм
Note This type of tower can be used on 150kV overhead lines. Towers are normal for overhead lines with up to АС120 wires and they are light (designed for one broken wire) for overhead lines with up to АС150 wires.

У110-4Н

Product Name У110-4Н У110-4Н+5 У110-4Н
Glaze Ice Region I-IV I-IV
Wind Region III III
Wind Region АС-70 ÷ АС-150 АС-70 ÷ АС-150
Dimensions in Foundation Axis L, m 4,1 5,6
Tower Height Н, m 23,9 28,9
Height up to Lower Crossarm h, m 10,5 15,5
Weight of Tower with Zinc Coating, kg 4798 6199
Номер типового проекта 5778тм
Note The upper section of the tower is welded and coated with cold zinc. Towers are similar to У110-4. This type of tower can be used on 150kV overhead lines. Towers are normal for overhead lines with up to АС120 wires and they are light (designed for one broken wire) for overhead lines with up to АС150 wires.

1У110-2

Product Name 1У110-2 1У110-2+5 1У110-2+10 1У110-2+15 1У110-2
Glaze Ice Region I-IV I-IV I-IV I-IV
Wind Region III III III III
Wire Model АС-120 АС-120 АС-120 АС-120
Dimensions in Foundation Axis L, m 3,78 5,03 6,28 7,53
Tower Height Н, m 22,6 27,6 32,6 37,6
Height up to Lower Crossarm h, m 8,6 13,6 18,6 23,6
Weight of Tower with Zinc Coating, kg 4443 6158 7595 9340
Standard Project Number 3.407.2-170
Note Spacers can be used with this type of tower (spacer weight is not specified). Lightning rod is delivered based on a separate order.

1У110-4

Product Name 1У110-4 1У110-4+5 1У110-4+10 1У110-4+15 1У110-4
Glaze Ice Region I-IV I-IV I-IV I-IV
Wind Region III III III III
Wire Model АС-240 АС-240 АС-240 АС-240
Dimensions in Foundation Axis L, m 4,08 5,33 6,58 7,83
Tower Height Н, m 22,6 27,6 32,6 37,6
Height up to Lower Crossarm h, m 8,6 13,6 18,6 23,6
Weight of Tower with Zinc Coating, kg 5853 7834 9543 12063
Standard Project Number 3.407.2-170
Note Spacers can be used with this type of tower (spacer weight is not specified). Lightning rod is delivered based on a separate order.

1У110-4П

Product Name 1У110-4П 1У110-4П+5 1У110-4П+10 1У110-4П+15 1У110-4П
Glaze Ice Region I-IV I-IV I-IV I-IV
Wind Region III III III III
Wire Model АС-240 АС-240 АС-240 АС-240
Dimensions in Foundation
Axis L, m
4,08 5,33 6,58 7,83
Tower Height Н, m 22,6 27,6 32,6 37,6
Height up to Lower Crossarm h, m 8,6 13,6 18,6 23,6
Weight of Tower with Zinc Coating, kg 5981 7963 9671 12193
Standard Project Number 3.407.2-166
Note Towers used at transition point to vertical configuration (two tiers). Spacers can be used with this type of tower (spacer weight is not specified). Lightning rod is delivered based on a separate order.

1У110-8

Product Name 1У110-8 1У110-8
Glaze Ice Region I-IV
Wind Region III
Wire Model АС-240
Dimensions in Foundation Axis L, m 4,08
Tower Height Н, m 34.66
Height up to Lower Crossarm h, m 8.66
Weight of Tower with Zinc Coating, kg 10205
Standard Project Number 3.407.2-166

УС110-6

Product Name УС110-6 УС110-6
Glaze Ice Region I-IV
Wind Region III
Wire Model АС-70 ÷ АС-240
Dimensions in Foundation Axis L, m 3,5
Tower Height Н, m 29,7
Height up to Lower Crossarm h, m 15,5
Weight of Tower with Zinc Coating, kg 10826
Standard Project Number 3079тм
Note

Towers designed for in-town use. Towers can be used on 35kV overhead
lines. Towers are used when PTL turn angle is limited.

У110-2ТС

Product Name У110-2ТС У110-2ТС+5 У110-2ТС+14 У110-2ТС
Glaze Ice Region I-IV I-IV I-IV
Wind Region III III III
Wire Model АС-70 ÷ АС-240 АС-70 ÷ АС-240 АС-70 ÷ АС-240
Dimensions in Foundation Axis L, m 4,8 6,3 8,9
Tower Height Н, m 24,6 29,6 38,6
Height up to Lower Crossarm h, m 10,5 15,5 24,5
Weight of Tower with Zinc Coating, kg 7473 9388 14998
Standard Project Number 3.407-119
Note Унифицированная опора с применением тонкостенных угловых профилей.