Control Cables

АКВВГ

Model Design Number of Strands Wire Cross-Section, mm 2 Purpose of Use
АКВВГ Current-conducting aluminum cable strands: insulated with PVC plasticate, twisted into concentric layers and covered with PVC plasticate. 4 - 61 2,5-6,0

Used for fixed connection to electrical devices and equipment, terminal blocks of electrical substations with nominal AC voltage up to 660 V and frequency up to 1000 Hz or DC voltage up to 1000 V.

Laid indoors, ducts, tunnels, in corrosive environments, without significant mechanical impact on the cable.

КВВГ

Model Design Number of Strands Wire Cross-Section, mm 2 Purpose of Use
КВВГ Current-conducting copper cable strands: insulated with PVC plasticate, twisted into concentric layers and covered with PVC plasticate. 4 - 61 0,75-6,0

Used for fixed connection to electrical devices and equipment, terminal blocks of electrical substations with nominal AC voltage up to 660 V and frequency up to 1000 Hz or DC voltage up to 1000 V.

Laid indoors, ducts, tunnels, in corrosive environments, without significant mechanical impact on the cable.

АКВВГЭ

Model Design Number of Strands Wire Cross-Section, mm 2 Purpose of Use
АКВВГЭ

Current-conducting aluminum cable strands: insulated with PVC plasticate and twisted into concentric layers.
Twisted strands are wrapped and shielded using aluminum foil. Cable sheath is made from PVC plasticate.

4 - 61 2,5-6,0 Laid indoors, ducts, tunnels without mechanical impact on the cable in corrosive environments and without requirement to protect electrical circuits from exposure to external electric fields.

КВВГЭ

Model Design Number of Strands Wire Cross-Section, mm 2 Purpose of Use
КВВГЭ Current-conducting copper cable strands: insulated with PVC plasticate and twisted into concentric layers. Twisted strands are wrapped and shielded using aluminum foil. Cable sheath is made from PVC plasticate. 4 - 61 0,75-6,0 Laid indoors, ducts, tunnels without mechanical impact on the cable in corrosive environments and without the requirement to protect electrical circuits from exposure to external electric fields.

АКВБбШв

Model Design Number of Strands Wire Cross-Section, mm 2 Purpose of Use
АКВБбШв Current-conducting aluminum cable strands: insulated with PVC plasticate and twisted into concentric layers. Twisted strands are wrapped and armored using two galvanized steel strips. Cable sheath is made from PVC plasticate. 4 - 61 2,5-6,0 Used for fixed connection to electrical devices and equipment, terminal blocks of electrical substations with nominal AC voltage up to 660 V and frequency up to 1000 Hz or DC voltage up to 1000 V. Laid indoors, ducts, tunnels. Buried in soil (tranches) in corrosive environments and in places exposed to earth currents, when cables are not exposed to tensile stress.

КВБбШв

Model Design Number of Strands Wire Cross-Section, mm 2 Purpose of Use
КВБбШв Current-conducting copper cable strands: insulated with PVC plasticate and twisted into concentric layers. Twisted strands are wrapped and armored using two galvanized steel strips. Cable sheath is made from PVC plasticate. 4 - 61 0,75-6,0 Used for fixed connection to electrical devices and equipment, terminal blocks of electrical substations with nominal AC voltage up to 660 V and frequency up to 1000 Hz or DC voltage up to 1000 V. Laid indoors, ducts, tunnels. Buried in soil (tranches) in corrosive environments and in places exposed to earth currents, when cables are not exposed to tensile stress.