Double circuit intermediate tension poles

П330-2

Product Name П330-2 П330-2
Glaze Ice Region I-IV
Wind Region III
Wire Model АС-300 ÷ АС-400
Dimensions in Foundation Axis L, m 5,75х3,683
Tower Height Н, m 43,5
Height up to Lower Crossarm H, m 22,5
Weight of Tower With Zinc Coating kg 10778
Standard Project Number 3080тм

3П330-2

Product Name 3П330-2Т 3П330-2т-5,0 3П330-2т-11,5 3П330-2Т
Glaze Ice Region I-IV I-IV I-IV
Wind Region I-III I-III I-III
Wire Model АС240 ÷ АС400 АС240 ÷ АС400 АС240 ÷ АС400
Dimensions in Foundation Axis L, m 4,4х6,07 5,34х4,03 3,54х4,37
Tower Height Н, m 49,5 44,5 38,0
Height up to Lower Crossarm H, m 26,0 21,0 14,5
Weight of Tower With Zinc Coating kg 11258 10154 8678
Standard Project Number 3.407.2-156
Note Tower designed for areas with polluted air. Towers with ground wire support for two cables.

П330-2Т

Product Name П330-2Т П330-2Т
Glaze Ice Region I-IV
Wind Region III
Wire Model АС-300 ÷ АС-400
Dimensions in Foundation Axis L, m 5,75х3,683
Tower Height Н, m 44,0
Height up to Lower Crossarm H, m 22,5
Weight of Tower With Zinc Coating kg 11087
Standard Project Number 3080тм
Note Towers with ground wire support for two cables.

3П330-2Т

Product Name 3П330-2Т 3П330-2т-5,0 3П330-2т-11,5 3П330-2Т
Glaze Ice Region I-IV I-IV I-IV
Wind Region I-III I-III I-III
Wire Model АС240 ÷ АС400 АС240 ÷ АС400 АС240 ÷ АС400
Dimensions in Foundation Axis L, m 4,4х6,07 5,34х4,03 3,54х4,37
Tower Height Н, m 49,5 44,5 38,0
Height up to Lower Crossarm H, m 26,0 21,0 14,5
Weight of Tower With Zinc Coating kg 11258 10154 8678
Standard Project Number 3.407.2-156
Note Tower designed for areas with polluted air. Towers with ground wire support for two cables.

ПС330-2

Product Name ПС330-2 ПС330-2
Glaze Ice Region I-IV
Wind Region III
Wire Model АС-300 ÷ АС-400
Dimensions in Foundation Axis L, m 5,17х3,38
Tower Height Н, m 38,5
Height up to Lower Crossarm H, m 17,5
Weight of Tower With Zinc Coating kg 9548
Standard Project Number 3080тм